Product Information

The 1 to 16 Zones Conventional Fire Alarm Control Panel is a robust and highly efficient fire detection system suitable for commercial and industrial applications. It is designed with advanced features to ensure reliability and ease of use, making it an ideal choice for fire safety management.

 

Key Specifications

 

Zones: 1 to 16 zones for fire detection coverage

Main Voltage: 220-230V AC, 50/60 Hz

System Voltage: 24V DC

Zone Voltage: 21V DC

Sounder Alarm Output: 2 outputs, each at 400mA @ 24V DC

Fault Relay Output: 1x relay (1A max)

Fire Relay Output: 1x relay (1A max)

Battery and Power Management

 

Battery Capacity: Space for up to 2 x 7AH 12V rechargeable batteries

Battery Charger Protection: Includes short circuit and thermal overcharge protection

Zone Short Circuit Protection: Ensures integrity of detection line even if a detector is removed, with no need for active End of Line (EOL) devices

Key Features

 

Microprocessor-Based Detection: High reliability with detector removal line integrity

Relay Outputs: Fire and fault changeover relay outputs for integration with other systems

Isolate Facility for Each Zone: Allows individual zones to be isolated as needed

Front Panel Indicators: Short circuit and earth fault indications displayed on the front panel

Programmable Sounder Delay: Adjustable delay for external sounders (0-9 minutes in 1-minute increments)

One-Person Test Mode: Simplifies testing for single-person operation

Easy Installation: Designed with top, bottom, and rear cable entries for flexible setup

IP Rating: IP43 for moderate protection against dust and water ingress

Applications

This 1 to 16 Zones Conventional Fire Alarm Control Panel is ideal for buildings where fire detection in multiple zones is critical. Its user-friendly features and safety protections make it suitable for use in a variety of environments, from office buildings to manufacturing facilities.

Size