Product Information
Key features
Addressable: The call point is connected to and monitored by a fire alarm control panel, providing the exact location of the alarm trigger.
Resettable element: Unlike traditional “break glass” call points, the S4-34845 uses a flexible element that can be reset with a special key after an alarm is triggered, without needing to replace any parts.
Protective cover: A hinged, lift-up protective cover prevents accidental or malicious activation of the alarm.
Built-in isolator: The unit includes a built-in short-circuit isolator to ensure loop integrity in the event of a wiring fault.
LED indicators: The call point features an LED status indicator for quick visibility. A red LED indicates a fire alarm, while a yellow tab becomes visible upon activation.
Ultra-fast response time: The device boasts a response time of less than one second.
Versatile mounting: The unit can be flush-mounted into a wall or surface-mounted with a separate back box.
Technical specifications
Case material: ABS engineering plastic.
Color: Red.
Dimensions (WxHxD): 88mm x 88mm x 21mm (flush-mounted). For surface mounting, it measures 57mm deep with a back box.
Weight: Approximately 110g.
Operating voltage: 35V to 41V.
Compliance: EN54-11 and EN54-17 compliant.
Installation and usage
Compatibility: The S4-34845 is designed exclusively for use with Gent’s Vigilon and Nano fire alarm control panels.
Resetting: To reset the call point after activation, a test key is inserted into a keyhole under the protective cover. Turning the key will return the call point to a normal, un-alarmed state.
Testing: A test key is also used for routine testing to simulate an alarm and ensure correct operation.