Product Information
Specifications
- Zones: 1 to 16 zones for fire detection coverage
- Main Voltage: 220-230V AC, 50/60 Hz
- System Voltage: 24V DC
- Zone Voltage: 21V DC
- Sounder Alarm Output: 2 outputs, each at 400mA @ 24V DC
- Fault Relay Output: 1x relay (1A max)
- Fire Relay Output: 1x relay (1A max)
Battery and Power Management
- Battery Capacity: Space for up to 2 x 7AH 12V rechargeable batteries
- Battery Charger Protection: Includes short circuit and thermal overcharge protection
- Zone Short Circuit Protection: Ensures integrity of detection line even if a detector is removed, with no need for active End of Line (EOL) devices
Key Features
- Microprocessor-Based Detection: High reliability with detector removal line integrity
- Relay Outputs: Fire and fault changeover relay outputs for integration with other systems
- Isolate Facility for Each Zone: Allows individual zones to be isolated as needed
- Front Panel Indicators: Short circuit and earth fault indications displayed on the front panel
- Programmable Sounder Delay: Adjustable delay for external sounders (0-9 minutes in 1-minute increments)
- One-Person Test Mode: Simplifies testing for single-person operation
- Easy Installation: Designed with top, bottom, and rear cable entries for flexible setup
- IP Rating: IP43 for moderate protection against dust and water ingress