Product Information

Key features

Addressable: The call point is connected to and monitored by a fire alarm control panel, providing the exact location of the alarm trigger.

Resettable element: Unlike traditional “break glass” call points, the S4-34845 uses a flexible element that can be reset with a special key after an alarm is triggered, without needing to replace any parts.

Protective cover: A hinged, lift-up protective cover prevents accidental or malicious activation of the alarm.

Built-in isolator: The unit includes a built-in short-circuit isolator to ensure loop integrity in the event of a wiring fault.

LED indicators: The call point features an LED status indicator for quick visibility. A red LED indicates a fire alarm, while a yellow tab becomes visible upon activation.

Ultra-fast response time: The device boasts a response time of less than one second.

Versatile mounting: The unit can be flush-mounted into a wall or surface-mounted with a separate back box.

Technical specifications

Case material: ABS engineering plastic.

Color: Red.

Dimensions (WxHxD): 88mm x 88mm x 21mm (flush-mounted). For surface mounting, it measures 57mm deep with a back box.

Weight: Approximately 110g.

Operating voltage: 35V to 41V.

Compliance: EN54-11 and EN54-17 compliant.

Installation and usage

Compatibility: The S4-34845 is designed exclusively for use with Gent’s Vigilon and Nano fire alarm control panels.

Resetting: To reset the call point after activation, a test key is inserted into a keyhole under the protective cover. Turning the key will return the call point to a normal, un-alarmed state.

Testing: A test key is also used for routine testing to simulate an alarm and ensure correct operation.

Size